Mandatory Replacement Years for Home Heat Tanks
Steel Thickness | Outlet/Connection Type | Mandatory Replacement Year |
---|---|---|
Non-metallic tanks | Not applicable | No mandatory replacement year |
Double-bottom metallic tank | Not applicable | No mandatory replacement year |
Metallic tank with nominal steel thickness of 2.0 mm |
Tank end or top burner connection | 15 years from year of tank manufacture |
Metallic tank with nominal steel thickness of 2.0 mm |
Bottom outlet burner connection | 20 years from year of tank manufacture |
Metallic tank with nominal steel thickness of 2.3 mm |
Tank end or top burner connection | 20 years from year of tank manufacture |
Metallic tank with nominal steel thickness of 2.3 mm |
Bottom outlet burner connection | 25 years from year of tank manufacture |
Who can I contact for more information?
Chief Boiler Inspector
J. Elmer Blanchard Building
31 Gordon Drive
Charlottetown, PE
Telephone: (902) 368-5567
Fax: (902) 368-5526